查看: 2296|回复: 2
收起左侧

[消防·救生] 厨房co2灭火系统

[复制链接]
头像被屏蔽
发表于 2021-5-7 08:31 | 显示全部楼层 |阅读模式 来自: 中国浙江
船方巡检提出:CO2 fire extiguishing system for vent trunk of galley room, the CO2 piping to be shifted in to Galley room to meet FSS requiement, Chapter 5, 2.1.3.1:The pipes may pass through accommodations providing that they are of substantial thickness and that their tightness is verified with a pressure test after their installation, at a pressure head not less than 5 N/mm2.  In addition, pipes passing through accommodation areas shall be joined only by welding and shall not be fitted with drains or other openings within such spaces.
Design reply:We will move the CO2 Nozzle to Galley图片复制下来的,比较模糊请大家谅解!发帖不易!
厨房通风管的 CO 2 灭火系统,根据 FSS 的要求,将 CO 2 管移到厨房第 5 章, 2 . 1 . 3 . 1 :管道可穿过舱室,但必须有足够的厚度,并在安装后在不低于 5 牛顿/平方毫米的压力下进行压力测试,以验证其密封性。此外,穿过住宿区的管道只能通过焊接连接,在这些空间内不得安装排水管或其他开口。
设计部回复:我们将把CO2喷嘴搬到厨房!

回复

使用道具 举报

龙船学院
发表于 2021-5-7 08:35 | 显示全部楼层 来自: 中国上海
这要看风闸装的位置
机械照搬一些所谓的公约规范,不去理解。。。。
回复 支持 反对

使用道具 举报

发表于 2021-5-7 10:18 | 显示全部楼层 来自: 中国江苏南通
vent trunk 灭火喷头不应该在vent trunk 里面吗?
回复 支持 反对

使用道具 举报

您需要登录后才可以回帖 登录 | 立即注册

本版积分规则

小黑屋|标签|免责声明|龙船社区

GMT+8, 2024-5-4 23:46

Powered by Imarine

Copyright © 2006, 龙船社区

快速回复 返回顶部 返回列表